INDEX
SECTION DESCRIPTION PAGE
1.0 General.......................................................................................... 6
2.0 Controller Specifications ............................................................ 6- 7
3.0 Installation .................................................................................... 7
3.1 Wiring Analog Output Module.................................................... 8-9
4.0 Analog Output Module Circuit Board Photo............................. 10
4.1 Analog Output Module Description and Operation .................11
5.0 Programming General.................................................................11
5.1 Analog Output Module Programming Codes ...........................12
5.2 Analog Output Module Programming Code Descriptions ...... 13-14
6.0 Remote Relay Output Module .................................................... 15
6.1 Remote Power Supply Module...................................................15
13
5.2 ANALOG OUTPUT MODULE PROGRAMMING CODE DESCRIPTIONS, CONT’D.
Calibrate Lower “1331” Limit and Upper “1332” Limit:
This function is for factory use
only. It allows a trained technician to calibrate each of the analog outputs. Before at-
tempting to perform this function, disable all of the channels of the PDC controller so
that the word “HOLD” appears on the digital display. A good digital multi-meter and
eight accurate (1%) 100 ohm, 1/4 watt resistors will be required to perform this function.
Lower Limit: Enable the output channel to be calibrated (normally all eight channels).
Terminate all outputs with a 100 ohm, 1% resistor. Attach the meter leads from the digi-
tal multi-meter to the test points “TP-1” and “TP-2”, for channel one. Set the meter range
to “0 to 2 volts”. Enter code “1331”. Use button “3” or “1” to increment or decrement the
meter value to achieve a reading of 0.400 +/- 1 digit. Press button “2” when done then
move the meter leads to the next channel. Repeat this process for all eight channels.
Upper Limit: Repeat the steps indicated above, using code “1332” and setting all meter
readings to 2.000 VDC. When done, you have completed the calibration process.
Note: All calibration values are stored on the analog output module circuit. That way if
the module is moved to another system, it will not have to be calibrated again.